Call Us Now
(044) 4383 1110

NEWGEN PFC UPS

1 KVA TO 3 KVA Online UPS

The deep impact from the house of UTL is a relatively new concept in the power sector. The deep impact of ups from the house of UTL packs all the features of an online ups in a compact form factor, further being transformer less the deep impact is extremely light and portable, making it easily installed in homes or even in offices. UTL'S DEEP impact range of online ups is a powerful, affordable and reliable backup option for your appliances.

Available from the ranges of 1 to 3 KVA in the DC voltages 12 & 36 volts the deep impact range of ups is a product that is capable of taking care of the backup needs of your computers along with the other appliances.

AVAILABLE IN
1 KVA in 12Volts & 36Volts
2 KVA & 3KVA IN 48 Volts and 72 Volts resp. (in R&D)

Pure Sine Wave Output

UTL's newGEN PFC online UPS is a MicroController, High Frequency PWM Technology Based "True Online" Double Conversion UPS System with IGBTs or MOSFETs at the Inverter Stage thus provides pure Sine wave output with high reliability and Efficiency. Making the newGEN PFC online UPS totally fit for running heavy loads like ACs, Industrial Motors and Pumps at gas stations etc. Even highly sensitive medical equipments such as life support systems work flawlessly with this ups.

Option for Ethernet connectivity

The newGEN PFC online UPS manufactured by the house of UTL has the option to connect to the internet via a built in Ethernet port at the back of the ups. When connected to the internet UTL'S newGEN PFC online UPS lets its user enjoy the freedom of monitoring its working from any where he likes may he be in any part of the world and be using any kind of internet device.

IGBT based charger

UTL's newGEN PFC online UPS turns out to be more like a savings account for the user. Being IGBT based this ups has a power factor of a whopping 0.9 where as it is just 0.7 in a parallel SCR has based ups. Because of having a power factor which is relatively higher the newGEN PFC online UPS helps to save upto 40% more power which in turn leads in large savings during its period of use.

Isolation transformer

newGEN PFC online UPS has an inbuilt isolation transformer, this helps in giving a better impedance match of a critical load to an electrical circuit. Totally fit for use in hospitals the isolation transformer in the newGEN PFC online UPS protects the sensitive equipments. UTL'S newGEN PFC online UPS suits Indian Power Conditions to its best making it installable anywhere from a hi-tech city to any village in India.

INPUT
Power Rating1 KVA (12V , 36V) ; 2KVA (48V) ; 3KVA (72V)
Voltage RangeSingle Phase - 22O V + 20 %
Frequency50 Hz + 5%
InputPowerFactor> 0.95
Electrical Connection6A, Indian Lead
OUTPUT
VoltageSingle Phase - 220V , 230V
Frequency50 Hz + 0.05%
Wave FormSine Wave
Transient Response<8(10%~90% Linear Load)
Voltage Harmonic< 3 % (Linear load)
Overload Capacity110% 30 sec, 111 to 150% : 18 sec, >150% :1 sec
Crest Factor3:1
DISPLAY
LEDBattery ON # Battery Low # Overload # Bypass # Mains High # Mains ON
LCD MeterOutput (Voltage & Frequency) # DC Voltage # Input (Voltage &Frequency) # Battery status # Load level
INTERFACE
Db9 / USBRS232 (Optional)
OVERALL
Efficiency (AC-AC)> 85**(FULL LOAD)
Transfer time0 ms
Temperature0 ~ 45 `C
Humidity5-95 %(Non -Condensed)