(044) 4383 1110

Industrial UPS - 5KVA to 300KVA

We provide isolation Transformer as a seperate part, wherever necessary to the senstive loads from abnormal input , which is highly increased the life of the load / equipments.

For three-phase output application, we import the basic module. Along with that we supplies other items like Bypass line equipment & Distribution board manufactured by us, Batteries procured from domestic battery vendors & integrate the system at site.

Special Features

  • True online double conversion design
  • IGBT inverter and output isolation transformer
  • Accurate synchronized utility system
  • Static bypass, allows system to be bypassed for maintenance operations
  • Allow 100% unbalance load
  • Double DSP control
  • 3x2 redundancy logic power design
  • Wide input voltage range
  • DC cold start function
  • Full protection function (short circuit, overload, over temperature, low battery etc)
  • Intelligent RS232/RS485 and dry connection interface, and flexible net project for monitoring via SNMP adapter (option)
Technical View
Nominal capacity KVA 10 KVA 20 KVA 30 KVA 40 KVA 60 KVA 80 KVA 100 KVA 120 KVA 160 KVA 300 KVA
Work principle Pure sine wave on line
Phase 3phase+N+G
Input power factor >0.8>0.95
Rectifier
Nominal input voltage 220/380VAC、230/400VAC、240/415VAC
Range ±25%
Nominal input frequency 50Hz±10% 60Hz±10%
Output ripple 2
Soft start 0100% 5sec
Charge
Charge mode constant current to constant voltage, with temp compensation; with Auto change
Float Voltage 432VDC
Boost Voltage 464VDC
Temperature compensation voltage 3mV/ 1 pcs
Charge current 0.1C automatically change follow the batteries
Charge frequency 20 of Rated capacity
Battery
Battery Type maintenance-free lead acid battery
Battery capacity 7 200AH settable (according to the capacity)
Battery number Nominal voltage 384VDC
Inverter
Phase Three phase+N
Capacity Rated capacity ×0.8
Battery voltage 220/380VAC 230/400VAC 240/415VAC
Output voltage stability ±1%( Stable load); ±3%( fluctuant load)
Output frequency stability 50Hz/60Hz ±0. 5%
Creast factor > 3:1
Output waveform distortion Sine wave ,linear load<3%;non-linear load<5%
Dynamic characteristics  Instant voltage<±5%(from 0 to100% ), Instant recover time<10mS
Unbalanced load voltage ±5%
Overload Protection 125%10 m 150%1S 200 200 ms
efficiency >95 full load
Bypass
Phase Three phase +N
Nominal voltage 220/380VAC 230/400VAC 240/415VAC
Transfer time <1mS( static switch with 0 transfer time )
Protection
Input protection Input voltage/frequency over limited ;wrong phase; lack phase
Output protection Over current short circuit ; factor low protection
Battery protection Over charge ; over-discharge protection
Temperature protection Ambient over temperature protection; inverter over temperature protection
Hardware failure protection Assistant power abnormal, breaker cut off ,breaker overload, power components over current/over voltage etc protection
System Parameters
Working environment Temp: 0 40, relative humidity 30%90 %;( a 1% decrease against 100 meters' rise. Altitude 4000m MAX)
cooling –down method COMPULSIVE VENTILATION(with temperature control)
Communication Interface RS232, RS485; optional SNMP card (for internet long distance monitor )
Redundancy function In series or N+1 parallel
Noise dB 48~55 55~60 60~65 65~70